Networked lighting controls

The other half of your LED retrofit incentive

An LED-only retrofit earns ComEd's standard per-watt incentive. Add qualifying networked controls and two more layers apply: a higher fixture rate and a separate controls adder.

Whether you're mid-retrofit or upgrading controls on existing LED, the incentive math applies.

LED-only vs. LED + controls: how the incentive changes

Adding qualifying controls moves a ComEd LED retrofit from the standard LED-only rate to a materially higher combined incentive. The increase comes from two mechanisms: a higher NLC fixture rate and a separate controls adder that stacks on top.

  • LED-only baseline

    ComEd’s standard per-watt-reduced incentive for qualifying LED fixtures.

  • NLC fixture premium

    When networked lighting controls are included, the fixture portion steps above the LED-only baseline rather than stacking as a second fixture payment.

  • Controls adder

    A separate per-watt-controlled incentive stacks on top of the fixture rate when the controls package qualifies.

  • Combined effect

    Materially higher than an LED-only filing. We calculate the exact figure for your building during the assessment.

Additional location and sourcing bonuses can push coverage materially beyond the standard filing, depending on the project.

Incentive levels are set by ComEd's Energy Efficiency Program and reviewed annually. We confirm current rates for your project at assessment.

What happens to your energy bill after the rebate clears

Controls cut lighting energy consumption by an additional ~49% beyond what LED alone achieves — not from manufacturer projections, but from a study of 194 real commercial buildings tracked by NEEA and the DLC. Combined with LED's own 40–70% reduction, the total reaches 60–80% of baseline lighting energy, depending on existing conditions.

  1. Existing lighting load

    100%

  2. Remaining after LED retrofit

    ~45%

    LED retrofit reduction: 40–70%

  3. Final load with LED + NLC controls

    ~23%

    NLC controls: ~49% of the remaining load

Source: NEEA/DLC, Energy Savings from Networked Lighting Controls (2020), 194 commercial buildings.

64%

Offices

Additional NLC savings, median

68%

Warehouses

Additional NLC savings, median

<1%

Current penetration

Commercial luminaires with NLC

14%

By 2030

DOE projected market share

These reductions come from four control strategies working together: occupancy and vacancy sensing removes energy in unoccupied spaces, daylight harvesting dims fixtures near windows and skylights, high-end trim and task tuning reduce maximum output to match actual need, and scheduling aligns lighting with operating hours rather than leaving circuits on 24/7.

Your project may already require lighting controls

Illinois adopted the 2024 IECC effective November 30, 2025, incorporating ASHRAE 90.1-2022's expanded lighting-controls mandates. If your commercial lighting project exceeds the thresholds below, controls are not an upgrade — they are a code requirement.

  • All commercial interior lighting: automatic shutoff within 20 minutes of vacancy

    ASHRAE 90.1-2022 §9.4.1.1(b)

    Manual-only switches no longer comply. Applies to all commercial interior spaces regardless of size.

  • Sidelit and toplit zones with ≥75W general lighting require daylight-responsive controls

    ASHRAE 90.1-2022 §9.4.1.1(d), Addendum ba

    Threshold reduced from 150W in 90.1-2019. Continuous dimming to ≤20% plus OFF.

  • Open plan offices ≥300 sq ft: ≤600 sq ft per occupancy sensor zone

    ASHRAE 90.1-2022 §9.4.1.1(b)

    Enclosed offices ≤300 sq ft use the room as the control zone. The 600 sq ft maximum applies only to open plan areas.

  • Exterior lighting requires both schedule and occupancy-based reduction

    ASHRAE 90.1-2022 §9.4.1.4

    15-minute vacancy timeout. ≤1,500W per control zone. Daylight OFF control also required.

  • IECC 2024 replaces bilevel switching with continuous dimming

    2024 IECC §C405.2

    Full output to ≤10% plus OFF. Adds demand-responsive controls requirement. Energy monitoring threshold reduced to 10,000 sq ft from 25,000 sq ft.

  • Alterations affecting >50% of the lighting system trigger full controls requirements

    ASHRAE 90.1-2022 §9 Alterations

    For retrofit projects, the scope of the lighting alteration — not the age of the building — determines whether current controls mandates apply. A large enough LED retrofit independently triggers ASHRAE 90.1-2022 compliance.

  • Effective November 30, 2025 — already in effect statewide

    Illinois Capital Development Board, 2024 IECC adoption

    Illinois statewide. Projects within Chicago city limits should verify requirements with Chicago DOB under the 2022 Energy Transformation Code.

Required controls by zone type

Zone typeControl requiredThreshold
InteriorAuto shutoff ≤20 minAll spaces
Sidelit / toplitDaylight dimming≥75W
Open office ≥300 sfOcc. sensor zones≤600 sf / zone
ExteriorSched. + occ. + daylight≤1,500W / zone
All zones (IECC)Continuous dimming≤10% + OFF

Illinois statewide, effective November 30, 2025. ASHRAE 90.1-2022 §9.4.1.1 and §9.4.1.4; 2024 IECC §C405.2.

References: ASHRAE 90.1-2022 Section 9, 2024 IECC Chapter C405, Illinois Capital Development Board.

What happens between ‘yes’ and ‘verified’

Most contractors install and leave — NLC systems that are not properly commissioned underperform or fail to qualify for ComEd incentives. Maplewood follows a 13-phase commissioning protocol from pre-application through post-occupancy verification, and manages the ComEd paperwork along the way.

  1. 1

    Pre-construction

    Pre-application → Reservation → Design

    ComEd pre-application submitted and reservation letter secured before installation begins. Owner's Project Requirements documented, Basis of Design established. Express reservations available for projects under $10K.

  2. 2

    Installation

    Equipment installation → Network formation

    DLC 5.1-listed fixtures and controllers installed. Network commissioned and communication verified. System architecture validated against Basis of Design.

  3. 3

    Configuration

    Device mapping → Logic configuration → Sensor calibration

    Every fixture mapped to its zone. Control logic programmed per OPR. Sensors calibrated to actual space conditions, not factory defaults.

  4. 4

    Optimization

    High-end trim → Task tuning

    Light output capped at actual need — 10–30% reduction typical from trim and tuning. This is where the energy-savings model gets realized. Uncalibrated systems save materially less.

  5. 5

    Verification & closeout

    Functional testing → Performance verification → Documentation

    Every control sequence tested against OPR. Zones that do not meet specification are recalibrated and retested before ComEd documentation is submitted. Energy baseline established for M&V. Owner handoff includes as-built report and end-user training.

ComEd coordination

We handle the paperwork

Maplewood manages pre-application, reservation, post-installation documentation, and incentive disbursement coordination — from initial filing through final payment.

What your equipment has to do to qualify

ComEd requires all networked lighting control equipment to be listed on the DLC Qualified Products List under current NLC5.1 standards — DLC 5.0 listings no longer qualify. Three domains determine eligibility.

  • Cybersecurity compliance

    Required under NLC5

    Mandatory device-level security — firmware signing, encrypted communications, access authentication.

  • Energy reporting

    NLC5.1 threshold

    Verified savings data at ≥15-minute intervals, reportable by time range, with storage history.

  • Interoperability

    NLC5.1 threshold

    Energy data sharing, occupancy data sharing, and external system integration via open protocols.

Independent verification

Equipment listed on the DLC Qualified Products List is publicly searchable. We specify listed equipment — you can verify it.

DLC Qualified Products List

Find out what controls would do for your building

Whether you're adding controls to a planned LED retrofit or upgrading an existing system for code compliance, the assessment shows you the specific opportunity for your building.

  • ComEd incentive estimate for your building
  • Code compliance review against current ASHRAE/IECC requirements
  • Recommended control strategy with projected energy savings
  • Complete scope and timeline if you decide to proceed

No cost. No commitment. Just the information you need to decide.